DEIF CM-2 Control Module Operational Guide
1. Functional Overview
- Multiparameter Monitoring: Voltage (0–690V AC), current (0–5A AC), frequency (45–65Hz), and power factor (0.5–1.0 lag/lead)5.
- HMI Interface: 5.7-inch graphical LCD with touchscreen for configuration (supports 10-user profiles)5.
- Communication Protocols:
- Ethernet (10/100BASE-T) for real-time data exchange
- RS-485 MODBUS RTU for legacy system integration5.
2. Startup Procedure
-
Pre-Power Checks
- Verify wiring integrity (terminals X1–X8 per IEC 60947).
- Ensure ESD protection (wrist strap required when handling PCB)4.
-
Initialization
- Apply 24V DC power (±10%); observe boot screen (3-sec diagnostic LED sequence).
- Navigate: Main Menu > System Calibration to zero-point adjust sensors.
-
Alarm Configuration
- Set thresholds via Settings > Alarms (e.g., overvoltage: +10% of nominal value).
- Enable SMS alerts if GSM module is installed5.
3. Safety & Maintenance
- Lockout/Tagout: Disconnect power before replacing fuses (F1/F2: 250V, 2A slow-blow).
- Data Backup: Export logs monthly via USB (Utilities > Data Export).
- Firmware Updates: Use DEIF ServiceTool v4.21+ (SHA-256 checksum mandatory)
CM-2 DEIF PDF