Fast delivery within 72 Hours

3625 TRICONEX 24VDC Digital Output Module

$422.00

Mandatory Validation Tests

test_sequenceCopy Code
1. TMR Integrity Test:
• Inject step signal (10%→90% FS)
• Verify voting consistency (%AIx_DIAG = 0)

2. Burnout Simulation:
• Open circuit on Ch4 → Confirm %ALMxx = 1

3. SIL Verification:
• PFDavg = 2.7E-9 (Mission time 10yr)
• SFF = 99.2%

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Triconex 3625 TMR Analog Input Module

Key Specifications

Parameter Value
Channels 16-channel differential (3× independent)
Input Range 0-10V, ±10V, 4-20mA (jumper-selectable)
Accuracy ±0.05% FS @ 25°C
CMV Rejection 140 dB @ 60Hz
TMR Voting 2oo3 mid-value selection
Update Rate 50 ms/channel
HART Support Revision 7 compliant


Installation Procedure

Step 1: Mechanical Mounting

plaintextCopy Code
1. Install in Tricon Chassis (e.g. 3700A/3805E)
• Slot compatibility: All non-comm slots
2. Torque backplane screws: 0.6 Nm ±0.05 Nm
3. Grounding: Connect chassis to earth via 6 AWG wire
- Impedance <0.1Ω to grounding bus

Step 2: Field Wiring

textCopy Code
[Termination Diagram]
CH1+ ───┤ IS Barrier ├─── +Field
CH1- ───┤ (e.g. 7868)├─── -Field
└─── 24V Ex ─┘

[Requirements]
• Shielded twisted pair (Belden 8761/equivalent)
• Max cable length: 250m (500m with repeater)
• Separation: ≥300mm from AC power cables


Configuration

DIP Switch Settings (Module Front)

Switch Position Function
SW1 ON HART enable
SW2-3 OFF-ON 4-20mA range
SW4 OFF Burnout detect ↑

 

TRISTATION 1131 Parameters

structured_textCopy Code
AI_BLOCK_CONFIG:
FILTER_TIME = 2.5 ; seconds
OUT_OF_RANGE_ALM = ±3%
VOTING_DISCREPANCY = 0.5% ; Tolerance

Safety-Critical Operations

 Hot-Swapping Protocol

  1. Place chassis in PROGRAM mode
  2. Execute command: TRICON STOP
  3. Wait for LED status:
    • Green OFF‌ + ‌Red FLASH‌ (safe to extract)

Ground Fault Detection

textCopy Code
Test Procedure:
1. Apply 25V AC between field wire and earth
2. Verify alarm: GFx bit in %S0003
3. Trip threshold: >5mA leakage

Diagnostics & Indicators

LED State Fault Condition
OK Red Channel disagreement
ACTIVE Green flashing Firmware update in progress
COMM Amber solid TMR comm sync failure

Troubleshooting Matrix

plaintextCopy Code
Fault Code: E105
Cause : Channel deviation >0.5% for 5s
Action : 1. Verify sensor calibration
2. Check HART multiplexer
3. Replace faulty sub-module


Certification & Compliance

plaintextCopy Code
- Functional Safety : IEC 61508 SIL 3 (HW Fault Tolerance=1)
- EMC : EN 61326-1 Class A (Industrial)
- Hazardous Areas : ATEX II 3G Ex ec [ia] IIC T4 Gc
- Seismic Rating : IEEE 693-2005 (High)

3625 TRICONEX    PDF

3625 TRICONEX

··········································································································

Our advantages:

1. The brand new product comes with a one-year

comprehensive warranty.

2. All products undergo strict quality inspections.

3. Contact us and our team will provide competitive

quotes and procurement plans.

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “3625 TRICONEX 24VDC Digital Output Module”

Your email address will not be published. Required fields are marked *