Validation Protocol

  1. Perform 3-point check:
    plaintextCopy Code
    0%: 4.00mA ±0.03mA
    50%: 12.00mA ±0.06mA
    100%: 20.00mA ±0.08mA
  2. Confirm HART revision: Device Rev. 3.1.2 or later

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Foxboro IDP10 Series Transmitter Installation

Pre-Installation Requirements

  1. Environmental Verification

    • Temperature Range: -40°C to +85°C (process) / -30°C to +70°C (electronics)
    • Ambient Humidity: ≤95% non-condensing
    • Atmospheric Compatibility: NACE MR0175/ISO 15156
  2. Process Interface

    plaintextCopy Code
    - Flange Standard: ASME B16.5 Class 300 RF
    - Material: 316L SST w/ Hastelloy C-276 diaphragm
    - Seal Options: FKM (Standard) / FFKM (Aqueous HCl)

Mechanical Installation Procedure

Step 1: Mounting Configuration

plaintextCopy Code
[Remote Seal Assembly]
1. Install capillary assembly with minimum bend radius R≥75mm
2. Orientation:
• Horizontal pipes: Sensor at 4 or 8 o'clock position
• Vertical pipes: Flow direction → HP port
3. Support capillary every 300mm (use P-clamps CAT #FXB-SUPP-10)

[Torque Specifications]
• Flange bolts: 45 Nm ±5% (crisscross pattern)
• Process connectors: 35 Nm (DN20) / 55 Nm (DN50)

Step 2: Pressure Balancing
CRITICAL ACTIONS

  • Equalize static pressure before power-up
  • Bleed air via vent screws (clockwise to close)
  • Confirm zero differential at startup


Electrical Installation

plaintextCopy Code
[Wiring Diagram]
Terminal + ───[24V PSU]───[250Ω Resistor]───[DCS AI]
Terminal - ────────────────────────────────────────

[Requirements]
• Cable: BELDEN 9501 (shielded twisted pair)
• Conductor: ≥1.5mm² (16 AWG)
• Intrinsic Safety: Use Foxboro ISB07 Barrier (EEx ia)
• Grounding: <1Ω to plant earth (terminal TB1)

Terminal Connections

Terminal Function Wire Color
+ Power Supply (18-36V DC) Brown
Signal Return Blue
G Ground Screw Green/Yellow

Commissioning Sequence

  1. Leak Test

    • Pressurize to 110% of range limit
    • Acceptable decay: ≤0.1% FS/hour
  2. Zero Calibration

    plaintextCopy Code
    a. Vent both HP/LP ports to atmosphere
    b. Using HART 475: Device Setup → Trim → Sensor Trim → Zero Trim
    c. Confirm output: 4.00mA ±0.02mA
  3. Damping Adjustment

    • Default: 0.4s (adjust via HART PD 1.3.4)
    • Turbulent flow recommendation: 2.5-5s


Safety & Compliance

plaintextCopy Code
EX Protection: ATEX II 1G Ex ia IIC T6 Ga
Certification: IECEx UL 17.0075X
EMC: EN 61326-1 (Industrial Immunity Level)

 ‌WARNINGS

  • Never apply voltage during capacitance check (damages EEPROM)
  • Avoid mounting near sources of >100V/m EMI
  • Seal conduits with Foxboro CPT-32 compound

Diagnostic Indicators

LED State Condition Action
Green solid Normal operation None
Yellow flashing (1Hz) Communication active HART session in progress
Red solid Sensor fault (ERR 38) Check diaphragm fill
Off Power loss Verify loop resistance

Loop Check:
Measure resistance: + to – terminals = 28Ω ±3Ω @25°C

 

 

P0500RY FOXBORO pdf

P0500RY FOXBORO

··········································································································

Our advantages:

1. The brand new product comes with a one-year

comprehensive warranty.

2. All products undergo strict quality inspections.

3. Contact us and our team will provide competitive

quotes and procurement plans.

 

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “P0500RY FOXBORO”

Your email address will not be published. Required fields are marked *