GE Multilin 369-HI-R-M-0-P1-0-E Motor Relay Commissioning Protocol

1. Pre-Commissioning Safety

 ‌Critical Measures‌:

  • De-energize motor circuit (NFPA 70E Category 3 PPE required)
  • Verify relay label: ‌“369-HI-R-M-0-P1-0-E”‌ (HI = High-Impedance Diff, P1 = Modbus RTU)
  • Confirm CT ratios match settings (e.g., ‌300:5‌ differential CTs)


2. Hardware Verification

Component Check Procedure Acceptance Criteria
CT Connections Insulation resistance test (2500V DC) >100 MΩ (phase-ground)
Control Power Measure Terminals L1/L2 110-240VAC ±10% (<2% THD)
Binary Inputs Dry contact closure test (TB3) Status change <15ms in EnerVista

► Use GEK-113487 test harness for CT injection


3. Relay Initialization

Front Panel Sequence‌:

mermaidCopy Code
graph LR
A[Press ENTER 3s] --> B[Initialize Settings]
B --> C[Select: Factory Defaults?]
C --> D[Confirm with SELECT key]
D --> E[Wait for STAT LED green]

Warning‌: Initialization erases custom settings!


4. Differential Protection Calibration

Slope Characteristic Test‌:

  1. Inject ‌20% I<sub>n</sub>‌ at Restrained Input (R)
  2. Inject ‌15% I<sub>n</sub>‌ at Operate Input (O)
  3. Verify ‌no trip‌ (Slope 1 = 15% typical)
  4. Repeat at ‌100% I<sub>n</sub>‌ with ‌60% I<sub>n</sub>‌ on O (Trip should occur @ Slope 2)

Settings‌:

textCopy Code
DIFF PICKUP: 0.3 x FLA
SLOPE 1: 15% │ SLOPE 2: 45%
BREAKPOINT: 4 x CT

5. Communication Setup (Modbus RTU)

Parameter Setting Verification Tool
Baud Rate 19.2 kbps ModScan read holding reg
Parity Even CRC error count = 0
Address DIP Switch 1-5 (e.g., 00101) Ping via RS-485 converter
Register Map 4xxxx (Motor status) EnerVista 369 SR3 software

► Termination resistor: 120Ω only for end-of-line units


6. Dynamic Functional Tests

Simulated Fault Sequence‌:

  1. Phase Loss‌: Disconnect L1 input → Trip in <100ms (Setpoint: 0.5s)
  2. Locked Rotor‌: Inject ‌600% FLA‌ → Trip @ 8s (Curve: I<sup>2</sup>t = ON)
  3. Ground Fault‌: Apply 25mA @ GF input → LED alarm (Pickup = 20mA)

Waveform Capture‌:

  • Trigger via front-panel RECORD button
  • Download .COMTRADE via USB (FTP://192.168.1.369)

7. Final Validation

Documentation Requirements
Test Record Sheet GE Form F6501-089 (signed by P.E.)
Setting Report EnerVista printed with password protection
IRIG-B Sync Verification ±1ms accuracy (Terminal TB4)

8. Critical Warnings

  • Never test differential protection without CT shorting blocks engaged
  • HI model requires minimum 15mA biasing current‌ (Check with clamp meter)
  • Modbus address conflict voids UL 1053 certification

···········································································································

Our advantages:
1. The brand new product comes with a one-year comprehensive warranty.
2. All products undergo strict quality inspections.
3. Contact us and our team will provide competitive quotes and procurement plans.

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “369-HI-R-M-0-P1-0-E GE”

Your email address will not be published. Required fields are marked *