Description

Bently Nevada 3500/42M Module Validation Procedure

Part No.:‌ 176449-02 | ‌Firmware:‌ v4.10+ | ‌Compliance:‌ API 670 5th Ed.


Pre-Test Requirements

  1. Safety Preparation

    • Verify chassis ground resistance ≤ 2 Ω (ANSI/IEEE C62.41)
    • Disconnect field wiring at TB3/TB4 terminals
    • Use ESD wrist strap (1 MΩ series resistance)
  2. Test Equipment

    • Calibrated DC source (Fluke 724/ProcessLINK compatible)
    • Precision shunt resistor: 250 Ω ±0.1% (for current loop simulation)
    • DIN rail power supply: 18-30V DC (ripple < 100mVpp)


Module Power-Up Verification

plaintextCopy Code
1. Apply 24V DC to PWR+/PWR- terminals (TB1)

2. Confirm indicators:
• PWR LED: Solid green
• FAIL LED: Off
• CHK CONFIG LED: Amber (should extinguish after 45s)

3. Measure backplane voltage:
• TP1-GND = -17.5V DC ±0.25V
• TP2-GND = -24V DC ±0.5V

Channel Functional Testing

Step 1: Proximitor Simulation

Channel Test Point Simulated Input Expected Reading Tolerance
Ch A J1-1 to J1-2 -18V DC 3500 SW: -17.8V ±0.15V
Ch B J2-1 to J2-2 -22V DC 3500 SW: -21.7V ±0.15V

Step 2: Current Loop Verification

plaintextCopy Code
1. Connect 250Ω shunt between Ch A OUT+ and OUT-
2. Apply -20V DC to Ch A IN+
3. Measure voltage across shunt:
• Normal operation: 1.00V DC = 4mA
• Alarm condition: 5.00V DC = 20mA (simulate gap voltage < -2V)

Diagnostic Fault Injection

Controlled Failure Modes:

plaintextCopy Code
[Test 1: Power Supply Fault]
- Reduce input voltage to 16.5V DC → FAIL LED flashes (1 Hz)

[Test 2: Sensor Open Circuit]
– Disconnect Ch B input →
• CHK CONFIG LED solid amber
• 3500 SW displays “SENSOR OPEN”

[Test 3: Over-temperature]
– Apply 150% load for 15min →
• Module auto-derates at 85°C
• Analog output clamped at 21.5mA


Post-Test Actions

  1. Performance Validation

    • Dynamic response test: 0.5-12 kHz sine sweep (settling time < 3ms)
    • Crosstalk rejection: ≤ -80 dB @ 10 kHz (per API 670 Sect. 4.9.3)
  2. Configuration Restore

    iniCopy Code
    [3500 Rack Config]
    Module_Type = 42M
    Firmware_Ver = 4.10
    Cal_Date = YYYY-MM-DD
    Damping_Filter = ON ; 2-pole Bessel

Critical Warnings

TEST PROHIBITIONS

  • Never exceed -30V DC input (irreversible Zener diode damage)
  • Do not hot-swap modules without rack isolator (PN 3500/15-01-01-00)
  • Avoid grounding OUT- terminals (causes current loop offset)

 ‌SAFETY INTERLOCKS

plaintextCopy Code
REQUIRED: Install transient suppressor (P/N 146449-01) when:
• Cable runs > 15m
• Location NEC Class I Div 2

3500/42 176449-02+128229-01 Bently Nevada PDF

3500-42 176449-02 128229-01 Bently Nevada

··········································································································

Our advantages:

1. The brand new product comes with a one-year

comprehensive warranty.

2. All products undergo strict quality inspections.

3. Contact us and our team will provide competitive

quotes and procurement plans.

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “3500/42 176449-02+128229-01 Bently Nevada”

Your email address will not be published. Required fields are marked *