Fast delivery within 72 Hours

Bently Nevada 3500/33 16 Channel Relay Module

$324.00

7. Troubleshooting

Symptom Action
LED not illuminated Check rack backplane voltage (P1-P2)
Contact welding Replace entire channel assembly
False triggering Verify SW2 test mode is OFF

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Bently Nevada 3500/33 Relay Module Operation Guide

Part Number: 3500/33-01-00-00 (4-channel configuration)


1. Safety Precautions

WARNING

  • Always de-energize the rack before module insertion/removal
  • Verify isolation voltage ≥250V AC between channels
  • Use CAT III-rated tools for terminal adjustments


2. Installation Procedure

Step 1: Mechanical Mounting

1. Insert into 3500 rack (slot positions 3-14) 2. Secure with M4 screws (torque 0.8 Nm ±10%) 3. Maintain ≥50mm clearance from high-voltage modules

Step 2: Electrical Connections

Terminal Function Specification
CH1-4 NO Normally Open Contact 8A @ 250V AC / 30V DC resistive
CH1-4 COM Common Terminal 16AWG stranded copper required
LED STATUS Diagnostic Output TTL level (5V DC max)


3. Configuration Steps

3.1 Software Setup (Using 3500 Rack Configuration Software v5.7+)

[Relay_Configuration] Channel_Delay=0.1s ; Activation delay Fault_Latch=ENABLED ; Requires manual reset Contact_Mode=FORM_C | Options: FORM_A/B/C

3.2 Hardware DIP Switches

SW1: Channel 1-4 enable/disable SW2: Test pulse mode (ON=50ms pulse)


4. Operational Verification

Test Sequence:

  1. Apply 24V DC to control input
  2. Measure contact resistance: ≤100mΩ when energized
  3. Verify LED indicators:
    • Green: Channel active
    • Red: Fault condition


5. Maintenance Requirements

  • Contact Life:
    • Mechanical: 10⁸ operations
    • Electrical: 10⁶ operations @ rated load
  • Calibration Interval: 12 months (per API 670)

6. Compliance Data

Standards: - IEC 60204-1 (Safety of machinery) - UL 508 (Industrial control equipment) Environmental: - Operating Temp: -40°C to +85°C - Humidity: 5-95% non-condensing

Bently Nevada 3500/33  16 Channel Relay Module  PDF

3500-33

··········································································································

Our advantages:

1. The brand new product comes with a one-year

comprehensive warranty.

2. All products undergo strict quality inspections.

3. Contact us and our team will provide competitive

quotes and procurement plans.

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Bently Nevada 3500/33 16 Channel Relay Module”

Your email address will not be published. Required fields are marked *