Woodward 5501-465 Digital Speed Control System
1. Core Performance Parameters
Parameter | Specification |
---|---|
Control Range | 20-12,000 RPM (±0.25% FS accuracy) |
Input Power | 18-36V DC (24V nominal) |
Load Sharing | ±0.5% droop adjustment |
Response Time | <100ms (10-90% step change) |
Communication | CANopen/J1939, RS-485 Modbus RTU |
2. Mechanical & Environmental
- Enclosure: NEMA 4X (IP66), aluminum alloy
- Operating Temp: -40°C to +85°C (derate 0.5%/°C >70°C)
- Vibration: 5-2000Hz @ 5G (IEC 60068-2-6)
- Mounting: DIN rail or direct bolt (M6×12mm)
3. Electrical Characteristics
Inputs:
- Speed sensing: Magnetic pickup (4-250V AC/DC)
- Aux analog: 4-20mA/0-10V (12-bit resolution)
Outputs:
- Actuator drive: 0-200mA PWM (1kHz carrier)
- Relay contacts: 5A @ 250V AC (NO/NC configurable)
Isolation:
- 1500V RMS input-to-output
- 500V channel-to-channel
4. Compliance & Safety
- Functional Safety: SIL 2 (IEC 61508)
- EMC: EN 61000-6-4 (Industrial immunity)
- Hazardous Areas: Class I Div 2 (ATEX pending)
5. Critical Notes
WARNINGS:
- Do not exceed 36V DC input – permanent damage risk
- Ground shield wires at single point only
- Calibration required after 50,000 operating hours
MAINTENANCE:
- Replace electrolytic capacitors every 10 years
- Use Woodward ProAct software for parameter tuning
5501-465 WOODWARD PDF
··········································································································
Reviews