Operational Validation

Step 5: Functional Testing

plaintextCopy Code
1. Channel Response Check:
- Inject step signal: 0-80% FS in 10ms
- Measure rise time: ≤15ms (per API 670)
2. Cross-talk Test:
- Energize Ch1 @ 8g - verify Ch2/3/4 <0.25%

3. Diagnostic Indicators:
| &zwnj;**LED**&zwnj; | &zwnj;**Normal**&zwnj; | &zwnj;**Fault**&zwnj; |
|--------------|------------|-------------------|
| OK (Green) | Solid | Off = HW failure |
| CH1 (Yellow) |

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

ABB VM600 Monitoring System: IOC4T Module Operation

MANDATORY PRECAUTIONS

  • De-energize associated sensors (accelerometers/proximitors) before connection
  • Verify floating ground configuration: Isolation voltage >250V DC (Channel-to-Backplane)
  • Wear ESD wrist strap (1MΩ resistance) during handling

Hardware Configuration

Step 1: Module Installation

plaintextCopy Code
1. Insert into VM600 rack slot: Position E4-E7 only (PNR200-560 requirement)
2. Engage locking levers: Apply 8 Nm torque until audible click

3. Grounding: Connect shield terminal (X1.13) to rack earth bar (≤0.1Ω continuity)

Step 2: Sensor Wiring

Terminal Signal Type Wiring Specification
X1.1-X1.4 ICP® Accelerometer RG-178 coaxial (max 300pF/m)
X1.5-X1.8 Proximitor (+24V EX) Twisted pair AWG20 (shielded)
X1.9 Common Sense Return 16mm² ground wire (star point)

Critical:‌ Maintain >50mm separation from power cables. Use ferrites (ABB FKC-45) for runs >15m.


Software Configuration (via Control Builder M)

Step 3: Module Initialization

iniCopy Code
[IOC4T_Config]
Slot_Address = E5 ; Match physical slot position
Sensor_Type = 4:Accel_SE ; 1=Proxim, 2=Temp, 3=Velom, 4=Accel
Excitation = 24V_DC@4mA ; For proximitor channels
Range = ±10g_peak ; Accelerometer full-scale

Step 4: Calibration Procedure

plaintextCopy Code
1. Apply calibration signal: 10.00V RMS @ 160Hz (Fluke 725 calibrator)

2. Execute auto-zero:
MEL > I/O Config > IOC4T > "Calibrate All"

3. Verify:
- Raw value tolerance: ±0.5% FS
- Noise floor: <2mV RMS (0.02% FS)

VM600 IOC4T PNR200-560-000-111 PDF

DS_VM600_IOC4T-en

···········································································································

Our advantages:

1. The brand new product comes with a one-year

comprehensive warranty.

2. All products undergo strict quality inspections.

3. Contact us and our team will provide competitive

quotes and procurement plans.

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “VM600 IOC4T PNR200-560-000-111”

Your email address will not be published. Required fields are marked *